Siemens 3RU2116-1BB0 là rơ-le nhiệt / rơ-le quá tải thuộc dòng SIRIUS 3RU2 / 3RB3. Mô tả đặt hàng theo Siemens: Overload relay 1.4...2.0 A Thermal For motor protection Size S00, Class 10 Contactor mounting Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic-Reset. Thông số nổi bật của 3RU2116-1BB0: Cỡ thiết bị: S00; Dải chỉnh dòng: 1.4 ... 2 A; Dòng định mức: 2 A; Công suất động cơ 400 V: 0.75 kW.

Thông số nổi bật 3RU2116-1BB0

Cỡ thiết bịS00
Dải chỉnh dòng1.4 ... 2 A
Dòng định mức2 A
Công suất động cơ 400 V0.75 kW
Số cực3
Kiểu sản phẩm3RU2
Kích thước (R×C×S)45 mm x 76 mm x 70 mm

Tóm tắt nhanh

Mã đặt hàng (MLFB)3RU2116-1BB0
Cách viết khác3RU21161BB0
Dòng sản phẩmSIRIUS 3RU2 / 3RB3
Loại thiết bịRơ-le nhiệt / rơ-le quá tải
Mô tả SiemensOverload relay 1.4...2.0 A Thermal For motor protection Size S00, Class 10 Contactor mounting Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic-Reset
Trạng thái vòng đờiĐang cung cấp P.M300 since 2009-11-19
Xuất kho tiêu chuẩn (Siemens)3 ngày
Khối lượng tịnh0.129 kg
Xuất xứĐức
Mã HS85364900
EAN4011209781603

Cam kết 3RU2116-1BB0 chính hãng, mới 100%

Thị trường có nhiều rơ-le nhiệt / rơ-le quá tải Siemens trôi nổi: hàng tháo máy, hàng tân trang, hàng sai phiên bản. Với 3RU2116-1BB0, Fast Group ghi rõ tình trạng mới 100% trong báo giá và chịu trách nhiệm nếu mã thực giao không khớp mã đặt hàng. Xem thêm: hàng Siemens chính hãng và hàng trôi nổi.

Trạng thái vòng đời và mã thay thế

3RU2116-1BB0 đang được Siemens sản xuất và cung cấp bình thường (PM300 từ 19/11/2009). Trạng thái kiểm tra trên SiePortal ngày 23/09/2026; xem thêm hàng Siemens ngừng sản xuất và mã thay thế.

So sánh 3RU2116-1BB0 với các mã cùng dòng SIRIUS 3RU2 / 3RB3

Bảng giúp chọn đúng mã trong cùng dòng trước khi gửi RFQ; bấm vào mã để xem chi tiết.

Mô tảThông số chínhTrạng thái
3RB3016-1RB0Overload relay 0.1...0.4 A Electronic For motor…Dải chỉnh dòng: 0.1 ... 0.4 A; Dòng định mức: 0.4 AĐang cung cấp
3RB3026-1RB0Overload relay 0.1...0.4 A Electronic For motor…Dải chỉnh dòng: 0.1 ... 0.4 A; Dòng định mức: 0.4 AĐang cung cấp
3RU2116-1BB0 (đang xem)Overload relay 1.4...2.0 A Thermal For motor…Dải chỉnh dòng: 1.4 ... 2 A; Dòng định mức: 2 AĐang cung cấp
3RU2116-1FB0Overload relay 3.5...5.0 A Thermal For motor…Dải chỉnh dòng: 3.5 ... 5 A; Dòng định mức: 5 AĐang cung cấp
3RU2126-1KB0Overload relay 9.0...12.5 A Thermal For motor…Dải chỉnh dòng: 9 ... 12.5 A; Dòng định mức: 12.5 AĐang cung cấp
3RU2126-4AB0Overload relay 11...16 A Thermal For motor protection…Dải chỉnh dòng: 11 ... 16 A; Dòng định mức: 16 AĐang cung cấp

Nhà cung cấp 3RU2116-1BB0 Siemens uy tín: năm điều nên kiểm tra

Giá thấp nhưng thiếu chứng từ hoặc giao sai phiên bản sẽ đắt hơn nhiều khi dây chuyền phải dừng. Vì vậy Fast Group báo giá 3RU2116-1BB0 kèm tình trạng hàng, thời gian giao và danh mục chứng từ ngay từ đầu, để so sánh các nhà cung cấp trên cùng một mặt bằng. Xem thêm: checklist nhà cung cấp thiết bị Siemens.

Thông tin cần có khi gửi RFQ 3RU2116-1BB0

Ứng dụng tiêu biểu của SIRIUS: tủ MCC, tủ khởi động động cơ, bơm, quạt, máy nén và tủ điều khiển máy. Để báo giá nhanh, vui lòng gửi:

  • Mã MLFB
  • số lượng
  • hàng mới chính hãng hay surplus
  • firmware (CPU/HMI)
  • yêu cầu CO/CQ
  • thời gian cần hàng
  • địa điểm giao hàng
  • chấp nhận mã thay thế (Có/Không)
  • Ghi công suất/dòng định mức của động cơ và điện áp cuộn hút contactor.
  • Chọn kiểu đấu nối: bắt vít hay lò xo.

Thông số kỹ thuật 3RU2116-1BB0 theo datasheet

Bảng dưới đây trích từ datasheet Siemens (tiếng Anh) để tham khảo khi lập yêu cầu kỹ thuật; thông số cuối cùng được xác nhận khi báo giá. Tải datasheet PDF từ Siemens.

Thông tin chung (3)
product brand nameSIRIUS
product designationthermal overload relay
product type designation3RU2
General technical data (15)
size of overload relayS00
size of contactor can be combined company-specificS00
power loss [W] for rated value of the current at AC in hot operating state5.7 W
per pole1.9 W
type of calculation of power loss current-dependentquadratic
insulation voltage with degree of pollution 3 at AC rated value690 V
surge voltage resistance rated value6 kV
maximum permissible voltage for protective separation
in networks with ungrounded star point between auxiliary and auxiliary circuit440 V
in networks with grounded star point between auxiliary and auxiliary circuit440 V
in networks with ungrounded star point between main and auxiliary circuit440 V
in networks with grounded star point between main and auxiliary circuit440 V
shock resistance according to IEC 60068-2-278g / 11 ms
reference code according to IEC 81346-2F
Substance Prohibitance (day/month/year)10/01/2009
Net Weight0.129 kg
Ambient conditions (6)
installation altitude at height above sea level maximum2 000 m
ambient temperature
during operation-40 ... +70 °C
during storage-55 ... +80 °C
during transport-55 ... +80 °C
temperature compensation-40 ... +60 °C
relative humidity during operation10 ... 95 %
Main circuit (13)
number of poles for main current circuit3
adjustable current response value current of the current-dependent overload release1.4 ... 2 A
operating voltage
rated value690 V
at AC-3e rated value maximum690 V
operating frequency rated value50 ... 60 Hz
operational current rated value2 A
operational current at AC-3e at 400 V rated value2 A
operating power
at AC-3
at 400 V rated value0.75 kW
at 500 V rated value0.75 kW
at 690 V rated value1.1 kW
at AC-3e
at 400 V rated value0.75 kW
at 500 V rated value0.75 kW
at 690 V rated value1.1 kW
Auxiliary circuit (19)
design of the auxiliary switchintegrated
number of NC contacts for auxiliary contacts1
notefor contactor disconnection
number of NO contacts for auxiliary contacts1
notefor message "Tripped"
number of CO contacts for auxiliary contacts0
operational current of auxiliary contacts at AC-15
at 24 V3 A
at 110 V3 A
at 120 V3 A
at 125 V3 A
at 230 V2 A
at 400 V1 A
at 690 V0.75 A
operational current of auxiliary contacts at DC-13
at 24 V2 A
at 60 V0.3 A
at 110 V0.22 A
at 125 V0.22 A
at 220 V0.11 A
contact rating of auxiliary contacts according to ULB600 / R300
Protective and monitoring functions (2)
trip classCLASS 10
design of the overload releasethermal
UL/CSA ratings (2)
full-load current (FLA) for 3-phase AC motor
at 480 V rated value2 A
at 600 V rated value2 A
Short-circuit protection (1)
design of the fuse link
for short-circuit protection of the auxiliary switch requiredfuse gG: 6 A, quick: 10 A
Installation/ mounting/ dimensions (5)
mounting positionfor mounting on contactors: with a vertical mounting plane +/-135° rotatable & +/- 22.5° tiltable, stand-alone installation: with a vertical mounting plane +/-135° rotatable and +/-45° tiltable; for more details see manual
fastening methodContactor mounting
height76 mm
width45 mm
depth70 mm
Connections/ Terminals (16)
product component removable terminal for auxiliary and control circuitNo
type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control circuitscrew-type terminals
arrangement of electrical connectors for main current circuitTop and bottom
type of connectable conductor cross-sections
for main contacts
solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG cables for main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
type of connectable conductor cross-sections
for auxiliary contacts
solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
tightening torque
for main contacts with screw-type terminals0.8 ... 1.2 N·m
for auxiliary contacts with screw-type terminals0.8 ... 1.2 N·m
design of screwdriver shaftDiameter 5 ... 6 mm
size of the screwdriver tipPozidriv PZ 2
design of the thread of the connection screw
for main contactsM3
of the auxiliary and control contactsM3
Safety related data (5)
failure rate [FIT] with low demand rate according to SN 3192050 FIT
MTTF with high demand rate2 280 a
T1 value
for proof test interval or service life according to IEC 6150820 a
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Display (1)
display version for switching statusSlide switch
Approvals Certificates (9)
Environmental Product Declaration
global warming potential [CO2 eq] / during manufacturing0.921 kg
global warming potential [CO2 eq] / during sales0.0394 kg
global warming potential [CO2 eq] / during operation39 kg
global warming potential [CO2 eq] / after end of life-0.0145 kg
global warming potential [CO2 eq] / total39.9 kg
EnvironmentGeneral Product Approval
Environmental Confirmations
General Product ApprovalFor use in hazardous locations
otherRailway
MiscellaneousConfirmation
Further information (1)
Date9/22/2026Subject to change without notice© Copyright Siemens 2026

Câu hỏi thường gặp về 3RU2116-1BB0

3RU2116-1BB0 Fast Group cung cấp có phải hàng chính hãng, mới 100%?

Có. 3RU2116-1BB0 là hàng Siemens chính hãng, mới 100%, nguyên đai nguyên kiện, kèm CO/CQ theo lô. Fast Group không chào hàng tân trang hay đã qua sử dụng dưới danh nghĩa hàng mới.

Làm sao chọn nhà cung cấp 3RU2116-1BB0 uy tín?

Yêu cầu nhà cung cấp xác nhận mã MLFB đầy đủ, trạng thái vòng đời trên SiePortal, danh mục CO/CQ và thời gian giao bằng văn bản. Fast Group ghi đủ các mục này trong báo giá 3RU2116-1BB0.

3RU2116-1BB0 còn được Siemens sản xuất không?

3RU2116-1BB0 đang được Siemens sản xuất và cung cấp bình thường (PM300 từ 19/11/2009).

Làm sao để nhận báo giá 3RU2116-1BB0 nhanh nhất?

Gửi mã 3RU2116-1BB0, số lượng, thời gian cần hàng và nơi giao qua email minhduc@fastgroup.vn hoặc Zalo/điện thoại 0938 888 958, hoặc dùng biểu mẫu RFQ trên trang. Đủ thông tin, báo giá được lập trong ngày làm việc.

Nhận báo giá Siemens 3RU2116-1BB0

Gửi mã và số lượng qua email minhduc@fastgroup.vn hoặc Zalo/điện thoại (+84) 938 888 958, hoặc gửi RFQ qua biểu mẫu. Cam kết mới 100% chính hãng. Phản hồi trong ngày làm việc.