Siemens 3RW4422-1BC44 là khởi động mềm thuộc dòng SIRIUS 3RW. Mô tả đặt hàng theo Siemens: SIRIUS soft starter Values at 400 V, 40 °C standard: 29 A, 15 kW Inside-delta: 50 A, 22 kW 200-460 V AC, 230 V AC Screw terminals !!! Phased-out product !!! Successor is SIRIUS 3RW5, Preferred successor type is >>3RW5516-1HA14<<. Thông số nổi bật của 3RW4422-1BC44: Điện áp cuộn hút: 230 V; Số cực: 3; Công suất: 15 kW; Kích thước (R×C×S): 170 mm x 192 mm x 270 mm.

Tên gọi khác: soft starter; khởi động mềm.

Thông số nổi bật 3RW4422-1BC44

Điện áp cuộn hút230 V
Số cực3
Công suất15 kW
Kích thước (R×C×S)170 mm x 192 mm x 270 mm

Tóm tắt nhanh

Mã đặt hàng (MLFB)3RW4422-1BC44
Cách viết khác3RW44221BC44
Dòng sản phẩmSIRIUS 3RW
Loại thiết bịKhởi động mềm
Mô tả SiemensSIRIUS soft starter Values at 400 V, 40 °C standard: 29 A, 15 kW Inside-delta: 50 A, 22 kW 200-460 V AC, 230 V AC Screw terminals !!! Phased-out product !!! Successor is SIRIUS 3RW5, Preferred successor type is >>3RW5516-1HA14<<
Trạng thái vòng đờiNgừng sản xuất P.M490 since 2023-10-01
Xuất kho tiêu chuẩn (Siemens)3 ngày
Khối lượng tịnh5.014 kg
Xuất xứCộng hòa Séc
Mã HS85371098
EAN4011209625266

Trạng thái vòng đời và mã thay thế

3RW4422-1BC44 đã ngừng sản xuất (PM490 từ 01/10/2023). Fast Group cung ứng từ nguồn hàng còn lại hoặc mã kế nhiệm tương thích. Trạng thái kiểm tra trên SiePortal ngày 23/09/2026; xem thêm hàng Siemens ngừng sản xuất và mã thay thế.

So sánh 3RW4422-1BC44 với các mã cùng dòng SIRIUS 3RW

MãMô tảThông số chínhTrạng thái
3RW3026-1BB14Soft starter S0 25 A, 11 kW/400 V, 40 °C 200-480 V ACĐiện áp cuộn hút: 110 ... 230 V; Số cực: 3Đang cung cấp
3RW3036-1BB14Soft starter S2 45 A, 22 kW/400 V, 40 °C 200-480 V ACĐiện áp cuộn hút: 110 ... 230 V; Số cực: 3Đang cung cấp
3RW4026-1BB14Soft starter S0 25 A, 11 kW/400 V, 40 °C 200-480 V ACĐiện áp cuộn hút: 110 ... 230 V; Số cực: 3Đang cung cấp
3RW4036-1BB14Soft starter S2 45 A, 22 kW/400 V, 40 °C 200-480 V ACĐiện áp cuộn hút: 110 ... 230 V; Số cực: 3Đang cung cấp
3RW4422-1BC44 (đang xem)Soft starter Values at 400 V, 40 °C standard: 29 AĐiện áp cuộn hút: 230 V; Số cực: 3Ngừng sản xuất
3RW5214-1AC14Soft starter 200-480 V 18 A, 110-250 V AC Screw…Số ngõ vào số (DI): 1; Số ngõ ra số (DQ): 3Đang cung cấp
3RW5216-1AC14Soft starter 200-480 V 32 A, 110-250 V AC Screw…Số ngõ vào số (DI): 1; Số ngõ ra số (DQ): 3Đang cung cấp
3RW5225-1AC14Soft starter 200-480 V 63 A, 110-250 V AC Screw…Số ngõ vào số (DI): 1; Số ngõ ra số (DQ): 3Đang cung cấp

Cung ứng 3RW4422-1BC44 tại Fast Group

Fast Group – nhà cung cấp thiết bị Siemens chính hãng cho nhà máy và dự án – cung ứng 3RW4422-1BC44 với các hạng mục:

  • Xác nhận 3RW4422-1BC44 theo nhãn thiết bị hoặc BOM, bao gồm hậu tố phiên bản.
  • Cung ứng từ nguồn hàng còn lại, tình trạng hàng ghi rõ trong báo giá.
  • Hồ sơ CO, CQ, packing list, hóa đơn VAT và tờ khai hải quan theo yêu cầu đơn hàng; giao hàng toàn quốc.

Thông tin cho yêu cầu báo giá 3RW4422-1BC44

  • Mã MLFB
  • số lượng
  • hàng mới chính hãng hay surplus
  • firmware (CPU/HMI)
  • yêu cầu CO/CQ
  • thời gian cần hàng
  • địa điểm giao hàng
  • chấp nhận mã thay thế (Có/Không)

Thông số kỹ thuật 3RW4422-1BC44 theo datasheet

Bảng dưới đây trích từ datasheet Siemens (tiếng Anh) để tham khảo khi lập yêu cầu kỹ thuật; thông số cuối cùng được xác nhận khi báo giá. Tải datasheet PDF từ Siemens.

General technical data (15)
product brand nameSIRIUS
product designationSoft starter
product feature
integrated bypass contact systemYes
thyristorsYes
product function
intrinsic device protectionYes
motor overload protectionYes
evaluation of thermistor motor protectionYes
external resetYes
adjustable current limitationYes
inside-delta circuitYes
product component motor brake outputYes
insulation voltage rated value690 V
degree of pollution3, acc. to IEC 60947-4-2
reference code according to EN 61346-2Q
reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750G
Power Electronics (24)
operational current
at 40 °C rated value29 A
at 50 °C rated value26 A
at 60 °C rated value23 A
operational current for 3-phase motors at inside-delta circuit
at 40 °C rated value50 A
at 50 °C rated value45 A
at 60 °C rated value40 A
yielded mechanical performance for 3-phase motors
at 230 V
at standard circuit at 40 °C rated value5.5 kW
at inside-delta circuit at 40 °C rated value15 kW
at 400 V
at standard circuit at 40 °C rated value15 kW
at inside-delta circuit at 40 °C rated value22 kW
yielded mechanical performance [hp] for 3-phase AC motor at 200/208 V at standard circuit at 50 °C rated value7.5 hp
operating frequency rated value50 ... 60 Hz
relative negative tolerance of the operating frequency-10 %
relative positive tolerance of the operating frequency10 %
operating voltage at standard circuit rated value200 ... 460 V
relative negative tolerance of the operating voltage at standard circuit-15 %
relative positive tolerance of the operating voltage at standard circuit10 %
operating voltage at inside-delta circuit rated value200 ... 460 V
relative negative tolerance of the operating voltage at inside-delta circuit-15 %
relative positive tolerance of the operating voltage at inside-delta circuit10 %
minimum load [%]8 %
adjustable motor current for motor overload protection minimum rated value5 A
continuous operating current [% of Ie] at 40 °C115 %
power loss [W] at operational current at 40 °C during operation typical8 W
Control circuit/ Control (12)
type of voltage of the control supply voltageAC
control supply voltage frequency 1 rated value50 Hz
control supply voltage frequency 2 rated value60 Hz
relative negative tolerance of the control supply voltage frequency-10 %
relative positive tolerance of the control supply voltage frequency10 %
control supply voltage 1 at AC
at 50 Hz rated value230 V
at 60 Hz rated value230 V
relative negative tolerance of the control supply voltage at AC at 50 Hz-15 %
relative positive tolerance of the control supply voltage at AC at 50 Hz10 %
relative negative tolerance of the control supply voltage at AC at 60 Hz-15 %
relative positive tolerance of the control supply voltage at AC at 60 Hz10 %
display version for fault signalDisplay
Mechanical data (10)
width170 mm
height192 mm
depth270 mm
fastening methodscrew fixing
mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
required spacing with side-by-side mounting
upwards100 mm
at the side5 mm
downwards75 mm
wire length maximum500 m
number of poles for main current circuit3
Connections/ Terminals (24)
type of electrical connection
for main current circuitbox terminal
for auxiliary and control circuitscrew-type terminals
number of NC contacts for auxiliary contacts0
number of NO contacts for auxiliary contacts3
number of CO contacts for auxiliary contacts1
type of connectable conductor cross-sections for main contacts for box terminal using the front clamping point
solid2.5 ... 16 mm²
finely stranded with core end processing2.5 ... 35 mm²
finely stranded without core end processing4 ... 50 mm²
stranded4 ... 70 mm²
type of connectable conductor cross-sections for main contacts for box terminal using the back clamping point
solid2,5 ... 16 mm²
finely stranded with core end processing2.5 ... 50 mm²
finely stranded without core end processing10 ... 50 mm²
stranded10 ... 70 mm²
type of connectable conductor cross-sections for main contacts for box terminal using both clamping points
solid2x (2.5 ... 16 mm²)
finely stranded with core end processing2x (2.5 ... 35 mm²)
finely stranded without core end processing2x (4 ... 35 mm²)
stranded2x (4 ... 50 mm²)
type of connectable conductor cross-sections for AWG cables for main contacts for box terminal
using the back clamping point10 ... 2/0
using the front clamping point10 ... 2/0
using both clamping points2x (10 ... 1/0)
type of connectable conductor cross-sections for auxiliary contacts
solid2x (0.5 ... 2.5 mm²)
finely stranded with core end processing2x (0.5 ... 1.5 mm²)
type of connectable conductor cross-sections for AWG cables
for auxiliary contacts2x (20 ... 14)
for auxiliary contacts finely stranded with core end processing2x (20 ... 16)
Ambient conditions (9)
installation altitude at height above sea level5 000 m
environmental category
during transport according to IEC 607212K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
during storage according to IEC 607211K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
during operation according to IEC 607213K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
ambient temperature
during operation60 °C
during storage-25 ... +80 °C
derating temperature40 °C
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
UL/CSA ratings (6)
yielded mechanical performance [hp] for 3-phase AC motor
at 200/208 V
at inside-delta circuit at 50 °C rated value10 hp
at 220/230 V
at standard circuit at 50 °C rated value7.5 hp
at inside-delta circuit at 50 °C rated value15 hp
at 460/480 V
at standard circuit at 50 °C rated value15 hp
at inside-delta circuit at 50 °C rated value30 hp
contact rating of auxiliary contacts according to ULB300 / R300
Approvals Certificates (3)
EnvironmentGeneral Product Approval
Environmental Confirmations
EMVTest Certificates
Maritime applicationother
Further information (1)
Date9/21/2026Subject to change without notice© Copyright Siemens 2026

Câu hỏi thường gặp về 3RW4422-1BC44

3RW4422-1BC44 đã ngừng sản xuất chưa, mã thay thế là gì?

3RW4422-1BC44 đã ngừng sản xuất (PM490 từ 01/10/2023). Fast Group cung ứng từ nguồn hàng còn lại hoặc mã kế nhiệm tương thích. Gửi RFQ để kiểm tra phương án thay thế phù hợp.

Yêu cầu báo giá 3RW4422-1BC44 cần những thông tin gì?

Mã đầy đủ, số lượng, thời hạn cần hàng, địa điểm giao và yêu cầu chứng từ. Ghi công suất/dòng định mức của động cơ và điện áp cuộn hút contactor.

Yêu cầu báo giá

Thiết bị đang vận hành đã ngừng sản xuất: Quý khách vui lòng gửi ảnh nhãn hoặc mã đầy đủ để Fast Group xác nhận nguồn hàng và phương án thay thế.