ABB AFC40-30-00 – Contactor
Mã đặt hàng: 1SBL341001R3400, 1SBL341001R4200, 1SBL341001R5100, 1SBL341001R5500, 1SBL341001R8000, 1SBL341001R8100, 1SBL341001R8400, 1SBL341001R8500
Contactor ABB AFC40-30-00: 3 cực (3 NO), dòng định mức AC-3 40 A / 18.5 kW tại 400 V, AC-1 70 A, đầu nối bắt vít. Có 10 mã đặt hàng theo điện áp cuộn hút – chọn trong bảng bên dưới.
- Số cực
- 3P
- Tiếp điểm chính
- 3 NO
- AC-3 tại 400 V
- 40 A / 18.5 kW
- AC-1
- 70 A
- Đầu nối
- bắt vít
- Kích thước R × C × S
- 55 × 125.5 × 111 mm
- Khối lượng
- 0.98 kg
- Cấp bảo vệ
- IP10, IP20
- Chứng nhận
- UL, CCC, CB, CE, UKCA, DNV, ABS, BV
- Mã HS
- 85364900
Mã đặt hàng AFC40-30-00
| Mã đặt hàng | Model | Điện áp cuộn hút | EAN | Tình trạng | Datasheet |
|---|---|---|---|---|---|
| 1SBL341001R3400 | AFC40-30-00-34 | 175 V AC 50 Hz · 208 V AC 60 Hz | 3471523024366 | – | Trang ABB ↗ |
| 1SBL341001R4200 | AFC40-30-00-42 | 230–240 V AC 50 Hz · 277 V AC 60 Hz | 3471523023307 | – | Trang ABB ↗ |
| 1SBL341001R5100 | AFC40-30-00-51 | 400–415 V AC 50 Hz · 480 V AC 60 Hz | 3471523024380 | – | Trang ABB ↗ |
| 1SBL341001R5500 | AFC40-30-00-55 | 500 V AC 50 Hz · 600 V AC 60 Hz | 3471525003758 | – | Trang ABB ↗ |
| 1SBL341001R8000 | AFC40-30-00-80 | 220–230 V AC 50 Hz · 230–240 V AC 60 Hz | 3471523018730 | – | Trang ABB ↗ |
| 1SBL341001R8100 | AFC40-30-00-81 | 24 V AC 50/60 Hz | 3471523018754 | – | Trang ABB ↗ |
| 1SBL341001R8400 | AFC40-30-00-84 | 110 V AC 50 Hz · 110–120 V AC 60 Hz | 3471523018778 | – | Trang ABB ↗ |
| 1SBL341001R8500 | AFC40-30-00-85 | 380–400 V AC 50 Hz · 400–415 V AC 60 Hz | 3471523018792 | – | Trang ABB ↗ |
| 1SBL341001R8600 | AFC40-30-00-86 | 400–415 V AC 50 Hz · 415–440 V AC 60 Hz | 3471523023321 | – | Trang ABB ↗ |
| 1SBL341001R8800 | AFC40-30-00-88 | 230–240 V AC 50 Hz · 240–260 V AC 60 Hz | 3471523018815 | – | Trang ABB ↗ |
Thông số kỹ thuật
Thông số theo mã 1SBL341001R3400 (AFC40-30-00-34). Các mã còn lại trong bảng khác nhau chủ yếu ở điện áp cuộn hút – đối chiếu datasheet đúng mã khi đặt hàng.
Thông số kỹ thuật
| Number of Main Contacts NO | 3 |
|---|---|
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, UL 60335-2-40 LZGH2 A2L |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 40 A (440 V) 60 °C 40 A (500 V) 60 °C 35 A (690 V) 60 °C 25 A (380 / 400 V) 60 °C 40 A (220 / 230 / 240 V) 60 °C 40 A |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 40 A (440 V) 60 °C 40 A (500 V) 60 °C 35 A (690 V) 60 °C 25 A (380 / 400 V) 60 °C 40 A (220 / 230 / 240 V) 60 °C 40 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 22 kW (440 V) 22 kW (500 V) 22 kW (690 V) 22 kW (380 / 400 V) 18.5 kW (220 / 230 / 240 V) 11 kW |
| Rated Operational Power AC-3e (Pe) | (415 V) 22 kW (440 V) 22 kW (500 V) 22 kW (690 V) 22 kW (380 / 400 V) 18.5 kW (220 / 230 / 240 V) 11 kW |
| Rated Operational Power AC-6b (Pe) | (400 / 415 V) 40 °C, 50 / 60 Hz 26 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 20 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 26 kvar (440 V) 40 °C, 50 / 60 Hz 28.5 kvar (440 V) 55 °C, 50 / 60 Hz 65 kvar (440 V) 70 °C, 50 / 60 Hz 22 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 35 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 35 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 25 kvar (690 V) 40 °C, 50 / 60 Hz 46 kvar (690 V) 55 °C, 50 / 60 Hz 46 kvar (690 V) 70 °C, 50 / 60 Hz 34.5 kvar |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 1200 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 175 V 60 Hz 208 V |
| Coil Consumption | Average Holding Value 50 / 60 Hz 20 V·A Average Holding Value, from Warm State 6 W Average Pull-in Value 50 Hz 150 V·A Average Pull-in Value 60 Hz 151 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 18.4 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 6.4 W Holding at Max. Rated Control Circuit Voltage 60 Hz 22.4 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 7.8 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 168 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 216 V·A |
| Power Loss | at 6 A per Pole 0.1 W at Rated Operating Conditions AC-1 per Pole 3 W at Rated Operating Conditions AC-1 per Pole 3 W at Rated Operating Conditions AC-3 per Pole 1 W at Rated Operating Conditions AC-3 per Pole 1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 6 ... 19 ms Between Coil De-energization and NO Contact Opening 4 ... 14 ms Between Coil Energization and NC Contact Opening 3 ... 16 ms Between Coil Energization and NO Contact Closing 7 ... 21 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 4 ... 35 mm² Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² Rigid 1/2x 6 ... 3 5 mm² Rigid 1/2x 6 ... 35 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
| Wire Stripping Length | Control Circuit 10 mm Main Circuit 16 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Recommended Screw Driver | Pozidriv PZ |
| Tightening Torque | Control Circuit 1.2 N·m Main Circuit 4 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
Thông số UL/CSA
| NEMA Size | 2 |
|---|---|
| Continuous Current Rating NEMA | 45 A |
| Horsepower Rating NEMA | (115 V AC) Single Phase 3 Hp (200 V AC) Three Phase 10 Hp (230 V AC) Single Phase 7-1/2 Hp (230 V AC) Three Phase 15 Hp (460 V AC) Three Phase 25 Hp (575 V AC) Three Phase 25 Hp |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 60 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 3 hp (200 ... 208 V AC) Three Phase 10 hp (220 ... 240 V AC) Three Phase 15 (240 V AC) Single Phase 7-1/2 hp (440 ... 480 V AC) Three Phase 30 hp (550 ... 600 V AC) Three Phase 40 hp |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb Main Circuit 35 in·lb |
| Full Load Amps Motor Use | (120 V AC) Single Phase 34 A (200 ... 208 V AC) Three Phase 32.2 A (220 ... 240 V AC) Three Phase 42 A (240 V AC) Single Phase 40 A (440 ... 480 V AC) Three Phase 41 A (550 ... 600 V AC) Three Phase 40 A |
Kích thước & khối lượng
| Product Net Width | 55 mm |
|---|---|
| Product Net Depth / Length | 111 mm |
| Product Net Height | 125.5 mm |
| Product Net Weight | 0.98 kg |
Môi trường làm việc
| Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +60 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C |
|---|---|
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 25 g Closed, Shock Direction: B1 25 g Closed, Shock Direction: B2 15 g Closed, Shock Direction: C1 25 g Closed, Shock Direction: C2 25 g Open, Shock Direction: B1 5 g |
| Pollution Degree | 3 |
Đặt hàng
| Minimum Order Quantity | 1 piece |
|---|---|
| Customs Tariff Number | 85364900 |
Đóng gói
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 146.5 mm |
| Package Level 1 Depth / Length | 96.5 mm |
| Package Level 1 Height | 146.5 mm |
| Package Level 1 Gross Weight | 1.1 kg |
| Package Level 1 EAN | 3471523024366 |
Mã phân loại (ETIM, eClass, UNSPSC)
| Object Classification Code | Q |
|---|---|
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
Tài liệu
- Data Sheet, Technical Information 1SBC100219C0201Catalog / thông tin kỹ thuật
- Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 AccessoriesHướng dẫn lắp đặt
- Instructions and Manuals (Part 2) 1SAC200017M0002Hướng dẫn lắp đặt
- 2D & 3D Data AFC40-30-00-34CAD 2D/3D